Function Description
① This temperature controller has soft start mode, manual mode and automatic mode functions. The soft start mode is preheating and dehumidification function, which will not damage the heater due to mold humidity, thus extending the service life of the hot runner.
② Thermocouple type J or K is adjustable; temperature unit ℃ or ℉ is adjustable, displayed in PV window. Temperature setting range: 34-534℃
③ Input voltage: 220VAC±10% 50—60Hz or 110VAC±10% 50—60Hz, optional.
④ Multiple alarm and protection functions: low temperature alarm, high temperature alarm, temperature sensing wire disconnection alarm, temperature sensing wire reverse connection alarm, hot runner leakage protection alarm.
Technical Parameter Table Function Parameter Setting Table
Item | Code | Description | Factory Setting | ||
Input Voltage | 85V—250VAC | P01 | Temperature unit setting: can be set to ℃ or ℉ and displayed in SV display window | Factory setting: ℃ | |
Input Frequency | 50—60HZ | ||||
Operating Temperature | -10℃—55℃ | P02 | Alarm on/off setting: set to ON to activate alarm function, set to OFF to cancel alarm function | Factory setting: ON | |
Storage Temperature | -20℃—70℃ | ||||
Fuse Specification | 15A 250V ø6mm×30mm, 1‰sec | P03 | Control mode selection: PID control mode or F2y control mode | Factory setting: PID mode | |
Temperature Sensing Wire Model (Thermocouple Type) | K, J | ||||
Temperature Setting Range | 40℃—540℃ | P04 | Low temperature time setting: setting range 0—255S | Factory setting: 240S | |
Sampling Speed | 0.1S | ||||
Temperature Measurement Accuracy | ±0.1℃ | P05 | High temperature time setting: setting range 0—80S | Factory setting: 15S | |
Temperature Control Accuracy | ±1℃ | ||||
Output Voltage | 0—220V | P06 | Sensor model selection: K type or J type adjustable | Set according to customer requirements | |
Maximum Output Power | 3.6KW | ||||
Temperature Unit | ℃、℉ | P07 | Key on or lock selection: "uLc" for key on (usable); "Loc" for key locked (unusable) | Factory setting: "uLc" |